PROSOFT MVI56-PDPMV1 Master Network Interface Module The MVI56 PROFIBUS DP-V1 Master Network Interface Module allows ControlLogix processors to easily communicate with slave devices supporting PROFIBUS DP-V0 and DP-V1 protocol. The module acts as an input/output module between the PROFIBUS network,The MVI56-PDPMV1 is a communication module that functions as a Profibus DP V1 Master communication module, enabling any ControlLogix controller to connect with existing or new PROFIBUS network and communicate with up to 125 PROFIBUS slaves. This module is also compatible for use with PROFIBUS repeaters to maximize slave device connection . The module incorporates proprietary backplane technology that enables powerful data exchange with ControlLogix processors
The module acts as an input/output module between the PROFIBUS network and the ControlLogix processor. Data transfer from the processor is asynchronous with the I/O data transfer on the PROFIBUS network. Databases are user-defined and stored in the module to hold the data required by the protocol.
Specifications
Single Slot – 1756 backplane compatible
The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module
Ladder Logic is used for data transfer between module and processor. Sample ladder file (add-on instruction) included.
Local or remote rack
Configurable I/O backplane sizes allow optimal performance for remote rack applications
CIPconnect™ enabled. Module supports communications with ProSoft Configuration Builder and FDT comDTM via Ethernet routing using Rockwell Automation Ethernet interface.
Specification | Description |
Backplane Current Load | 800 mA @ 5.1 VDC 3mA @ 24 VDC |
Operating Temperature | 32° F to 140° F (0° C to 60° C) |
Storage Temperature | -40° F to 185° F (-40° C to 85° C) |
Shock | 30 g Operational 50 g non-operational |
Vibration | 5 g from 10 to 150 Hz |
Relative Humidity | 5% to 95% (without condensation) |
LED Indicators | Module Status
Backplane Transfer Status Application Status Serial Activity and Error LED Status |
Debug/Configuration port (CFG) | |
CFG Port (CFG) | RJ45 (DB-9M with supplied cable)
RS-232 only CIPconnect™ Ethernet routing using 1756-ENBT, 1756-EN2T or similar |
Shipped with Unit | RJ45 to DB-9M cables for each port
6-foot RS-232 configuration cable |