Get In Touch

Focused on industrial automation equipment spare parts for 20 years

Contacts
Location
1733 Luling Road, Siming District, Xiamen

PROSOFT MVI56-PDPMV1 Master Network Interface Module

PROSOFT MVI56-PDPMV1 Master Network Interface Module

PROSOFT MVI56-PDPMV1 Master Network Interface Module The MVI56 PROFIBUS DP-V1 Master Network Interface Module allows ControlLogix processors to easily communicate with slave devices supporting PROFIBUS DP-V0 and DP-V1 protocol. The module acts as an input/output module between the PROFIBUS network,The MVI56-PDPMV1 is a communication module that functions as a Profibus DP V1 Master communication module, enabling any ControlLogix controller to connect with existing or new PROFIBUS network and communicate with up to 125 PROFIBUS slaves. This module is also compatible for use with PROFIBUS repeaters to maximize slave device connection . The module incorporates proprietary backplane technology that enables powerful data exchange with ControlLogix processors

PROSOFT MVI56-PDPMV1

The module acts as an input/output module between the PROFIBUS network and the ControlLogix processor. Data transfer from the processor is asynchronous with the I/O data transfer on the PROFIBUS network. Databases are user-defined and stored in the module to hold the data required by the protocol.

Specifications

Single Slot – 1756 backplane compatible

The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module

Ladder Logic is used for data transfer between module and processor. Sample ladder file (add-on instruction) included.

Local or remote rack

Configurable I/O backplane sizes allow optimal performance for remote rack applications

CIPconnect™ enabled. Module supports communications with ProSoft Configuration Builder and FDT comDTM via Ethernet routing using Rockwell Automation Ethernet interface.

Specification Description
Backplane Current Load 800 mA @ 5.1 VDC
3mA @ 24 VDC
Operating Temperature 32° F to 140° F (0° C to 60° C)
Storage Temperature -40° F to 185° F (-40° C to 85° C)
Shock 30 g Operational
50 g non-operational
Vibration 5 g from 10 to 150 Hz
Relative Humidity 5% to 95% (without condensation)
LED Indicators Module Status

Backplane Transfer Status

Application Status

Serial Activity and Error LED Status

Debug/Configuration port (CFG)
CFG Port (CFG) RJ45 (DB-9M with supplied cable)

RS-232 only

CIPconnect™ Ethernet routing using 1756-ENBT, 1756-EN2T or similar

Shipped with Unit RJ45 to DB-9M cables for each port

6-foot RS-232 configuration cable

Please enable JavaScript in your browser to complete this form.

Reviews

There are no reviews yet.

Be the first to review “PROSOFT MVI56-PDPMV1 Master Network Interface Module”

Your email address will not be published. Required fields are marked *