PROSOFT MVI56-PDPMV1 Master Network Interface Module

PROSOFT MVI56-PDPMV1 Master Network Interface Module

PROSOFT MVI56-PDPMV1 Master Network Interface Module The MVI56 PROFIBUS DP-V1 Master Network Interface Module allows ControlLogix processors to easily communicate with slave devices supporting PROFIBUS DP-V0 and DP-V1 protocol. The module acts as an input/output module between the PROFIBUS network,The MVI56-PDPMV1 is a communication module that functions as a Profibus DP V1 Master communication module, enabling any ControlLogix controller to connect with existing or new PROFIBUS network and communicate with up to 125 PROFIBUS slaves. This module is also compatible for use with PROFIBUS repeaters to maximize slave device connection . The module incorporates proprietary backplane technology that enables powerful data exchange with ControlLogix processors

 

The module acts as an input/output module between the PROFIBUS network and the ControlLogix processor. Data transfer from the processor is asynchronous with the I/O data transfer on the PROFIBUS network. Databases are user-defined and stored in the module to hold the data required by the protocol.

 

Specifications

Single Slot – 1756 backplane compatible

The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module

Ladder Logic is used for data transfer between module and processor. Sample ladder file (add-on instruction) included.

Local or remote rack

Configurable I/O backplane sizes allow optimal performance for remote rack applications

CIPconnect™ enabled. Module supports communications with ProSoft Configuration Builder and FDT comDTM via Ethernet routing using Rockwell Automation Ethernet interface.

 

Specification

Description

Backplane Current Load

800 mA @ 5.1 VDC
3mA @ 24 VDC

Operating Temperature

32° F to 140° F (0° C to 60° C)

Storage Temperature

-40° F to 185° F (-40° C to 85° C)

Shock

30 g Operational
50 g non-operational

Vibration

5 g from 10 to 150 Hz

Relative Humidity

5% to 95% (without condensation)

LED Indicators

Module Status

Backplane Transfer Status

Application Status

Serial Activity and Error LED Status

Debug/Configuration port (CFG)

CFG Port (CFG)

RJ45 (DB-9M with supplied cable)

RS-232 only

CIPconnect™ Ethernet routing using 1756-ENBT, 1756-EN2T or similar

Shipped with Unit

RJ45 to DB-9M cables for each port

6-foot RS-232 configuration cable